Mati, AyacheBentarzi, Hamid2021-03-222021-03-222017978-1-5386-0687-2DOI: 10.1109/ICEE-B.2017.8192156https://ieeexplore.ieee.org/document/8192156https://dspace.univ-boumerdes.dz/handle/123456789/6650In this paper simulation studies have been conducted using Simulink/MATLAB software in order to investigate the impact of STATCOM on the positive-offset mho element loss of excitation (LOE) protection scheme in synchronous generator. The obtained results show that the operation of the positive-offset protection scheme takes more time under the integration of STATCOM in the transmission line. Moreover, an under reach phenomena may occur under partial loss of excitation (PLOE) condition of a generator with lightly loadingenLoss of Excitation (LOE)Partial LOETotal LOEImpact of STATCOM on generator positive-offset mho element loss of excitation protection(Article