Impact of STATCOM on generator positive-offset mho element loss of excitation protection
No Thumbnail Available
Date
2017
Authors
Journal Title
Journal ISSN
Volume Title
Publisher
IEEE
Abstract
In this paper simulation studies have been conducted using Simulink/MATLAB software in order to investigate the impact of STATCOM on the positive-offset mho element loss of excitation (LOE) protection scheme in synchronous generator. The obtained results show that the operation of the positive-offset protection scheme takes more time under the integration of STATCOM in the transmission line. Moreover, an under reach phenomena may occur under partial loss of excitation (PLOE) condition of a generator with lightly loading