Protection scheme enhancement of synchronous generator
No Thumbnail Available
Date
2021
Journal Title
Journal ISSN
Volume Title
Publisher
Université M'Hamed Bougara : Institut de génie électrique et électronique
Abstract
Synchronous generator is the most important element of a power system and its fast and
reliable protection is crucial. One of the most abnormal conditions in a generator is loss of
excitation (LOE) which is harmful to both the generator and the power system. This condition
should be detected and the generator isolated from the system to avoid generator damage as
well as power system instability.
This thesis presents a study and comparison of the two conventional LOE protection
schemes, negative-offset and positive-offset mho element under different conditions. The
results show that the two schemes can detect LOE fault under total or partial LOE conditions,
however in terms of speed (fault detection time) the positive offset scheme is faster than the
negative offset scheme under all loading conditions. Besides, the two LOE protection schemes
are reliable and do not operate under power swing disturbances caused by any type of external
faults.
Moreover, the impact of the static synchronous compensator (STATCOM) on the
positive-offset mho element LOE protection scheme is investigated. The obtained results show
that the operation of the positive-offset protection scheme takes more time under the integration
of STATCOM in the transmission line. Finally, to reduce this delay time, an enhanced method
based on phasor measurement unit (PMU) is proposed. The simulation results show that the
new developed method improves the operation of the positive offset mho element LOE
protection by reducing the delay time that may be due to the presence of STATCOM
Description
86 p. : ill. ; 30 cm
Keywords
Rotation speed, Excitation systems, Simulation studies